Air flow sensor SFAW-32T-TG12-E-PNLK-PNVBA-M12 8036872
Type codeSFAW
KC charactersKC EMC
Symbol00995566
CertificationRCM compliance mark
c UL us – Listed (OL)
CE marking (see declaration of conformity)As per EU RoHS directive
As per EU EMC directive
Note on materialsRoHS-compliant
Measured variableFlow rate
Temperature
Flow directionUnidirectional
P1 -> P2
Method of measurementTemperature: PT1000
Flow rate: vortex
Flow measuring range start value1.8 l/min
Flow measuring range end value32 l/min
Temperature measuring range start value0 °C
Temperature measuring range end value90 °C
Operating pressure0 bar … 12 bar
Information on operating pressureMax. 6 bar at 100 °C
Max. 12 bar at 40°C
Operating mediumWater
Neutral liquids
Liquid media
Information on operating and pilot mediaMedia with a kinematic viscosity = 1.8 mm²/sec. [cSt]. Compatibility of the media with the substances that come into contact with the media must be ensured.
Temperature of medium0 °C … 90 °C
Ambient temperature0 °C … 50 °C
Nominal temperature23 °C
Accuracy of flow rate±2 % FS for flow rate <= 50 % FS
±3 % o.m.v. for flow rate >= 50 %FS
Accuracy of temperature in ± °C2 °C
Repetition accuracy of flow rate value< ±0.5 % FS for flow rate <= 50 % FS
< ±1 % o.m.v. for flow rate >= 50 %FS
Temperature co-efficient margin in ± %FS/KTyp. ±0.05% FS/K
Switching output2 x PNP or 2 x NPN switchable
Switching functionWindow comparator
Threshold value comparator
Freely programmable
Switching element functionN/C contact/N/O contact switchable
Max. output current100 mA
Analog output4 – 20 mA
0 – 10 V
1 – 5 V
Flow rate curve start value0 l/min
Flow rate curve end value32 l/min
Temperature characteristic curve start value0 °C
Temperature characteristic curve end value100 °C
Max. load resistance of current output500 Ohm
Min. load resistance of voltage output15 kOhm
Short-circuit protectionyes
Overload protectionAvailable
ProtocolIO-Link®
IO-Link®, protocol versionDevice V 1.1
IO-Link®, profileSmart sensor profile
IO-Link®, function classesBinary data channel (BDC)
Diagnostics
Teach channel
Identification
Process data variable (PDV)
IO-Link®, communication modeCOM2 (38,4 kBd)
IO-Link®, SIO mode supportYes
IO-Link®, port classA
IO-Link®, process data width OUT0 Byte
IO-Link®, process data width IN5 Byte
IO-Link®, process data content IN1 bit BDC (temperature monitoring)
14 bit PDV (flow measurement)
1 bit BDC (volume monitoring)
2 bit BDC (flow monitoring)
14 bit PDV (temperature measurement)
IO-Link®, service data contents IN32 bit volume measurement
IO-Link®, minimum cycle time5 ms
IO-Link®, data memory required500 byte
DC operating voltage range18 V … 30 V
Reverse polarity protectionfor all electrical connections
Electrical connectionA-coded
5-pin
Plug, straight
M12x1
Max. cable length20 m for IO-Link® operation
30 m
Mounting positionAny
Fluid connectorInternal thread G1/2
Product weight400 g
Housing materialPA-reinforced
Materials in contact with the mediaEPDM (peroxide)
Stainless steel
ETFE
PA6T/6I-reinforced
Displayable unit(s)cft/min
l/h
°C
US gal
cft
m3
l
l/min
°F
US gal/min
Degree of protectionIP65
Corrosion resistance class (CRC)3 – High corrosion stress
Ordering data Design |
Part No. Type |
Clamped terminal connection | 8036883 SFAW-32-CS515-E-PNLK-PNVBA-M12 |
Female hose connector | 8036879 SFAW-32-S13-E-PNLK-PNVBA-M12 |
Female thread | 8036871 SFAW-32-TG12-E-PNLK-PNVBA-M12 |
8036873 SFAW-32-TG34-E-PNLK-PNVBA-M12 | |
User-specific connection | 8036887 SFAW-32-X-E-PNLK-PNVBA-M12 |
Clamped terminal connection | 8036884 SFAW-32T-CS515-E-PNLK-PNVBA-M12 |
Female hose connector | 8036880 SFAW-32T-S13-E-PNLK-PNVBA-M12 |
Female thread | 8036872 SFAW-32T-TG12-E-PNLK-PNVBA-M12 |
8036874 SFAW-32T-TG34-E-PNLK-PNVBA-M12 | |
User-specific connection | 8036888 SFAW-32T-X-E-PNLK-PNVBA-M12 |
Clamped terminal connection | 8036885 SFAW-100-CS520-E-PNLK-PNVBA-M12 |
Female thread | 8036877 SFAW-100-TG1-E-PNLK-PNVBA-M12 |
8036875 SFAW-100-TG34-E-PNLK-PNVBA-M12 | |
User-specific connection | 8036889 SFAW-100-X-E-PNLK-PNVBA-M12 |
Clamped terminal connection | 8036886 SFAW-100T-CS520-E-PNLK-PNVBA-M12 |
Female thread | 8036878 SFAW-100T-TG1-E-PNLK-PNVBA-M12 |
8036876 SFAW-100T-TG34-E-PNLK-PNVBA-M12 | |
User-specific connection | 8036890 SFAW-100T-X-E-PNLK-PNVBA-M12 |
Wall mounting | 8036909 SAMH-FW-W |
Seal | 8036907 SASF-FW-S-E |
Clip | 8036908 SAMH-FW-SB |
8036891 | SASA-FW-A-32-TG12 |
8036892 | SASA-FW-A-32-TG34 |
8036895 | SASA-FW-A-32-TR12 |
8036896 | SASA-FW-A-32-TR34 |
8036899 | SASA-FW-A-32-TN12 |
8036900 | SASA-FW-A-32-TN34 |
8036894 | SASA-FW-A-100-TG1 |
8036897 | SASA-FW-A-100-TR34 |
8036898 | SASA-FW-A-100-TR1 |
8036901 | SASA-FW-A-100-TN34 |
8036902 | SASA-FW-A-100-TN1 |
8036893 | SASA-FW-A-100-TG34 |
8036903 | SASA-FW-A-32-S13 |
8036904 | SASA-FW-A-32-S19 |
8036905 | SASA-FW-A-32-CS515 |
8036906 | SASA-FW-A-100-CS520 |
564930 SFAM-62-1000L-M-2SA-M12
564934 SFAM-62-3000L-M-2SA-M12
564938 SFAM-62-5000L-M-2SA-M12
564932 SFAM-62-1000L-M-2SV-M12
564936 SFAM-62-3000L-M-2SV-M12
564940 SFAM-62-5000L-M-2SV-M12
573346 SFAM-90-5000L-M-2SA-M12
573348 SFAM-90-10000L-M-2SA-M12
573350 SFAM-90-15000L-M-2SA-M12
573347 SFAM-90-5000L-M-2SV-M12
573349 SFAM-90-10000L-M-2SV-M12
573351 SFAM-90-15000L-M-2SV-M12
565375 SFAM-62-1000L-TG12-2SA-M12
565379 SFAM-62-3000L-TG12-2SA-M12
565383 SFAM-62-5000L-TG12-2SA-M12
565376 SFAM-62-1000L-TG12-2SV-M12
565380 SFAM-62-3000L-TG12-2SV-M12
565384 SFAM-62-5000L-TG12-2SV-M12
573352 SFAM-90-5000L-TG1-2SA-M12
573354 SFAM-90-10000L-TG112-2SA-M12
573356 SFAM-90-15000L-TG112-2SA-M12
573353 SFAM-90-5000L-TG1-2SV-M12
573355 SFAM-90-10000L-TG112-2SV-M12
573357 SFAM-90-15000L-TG112-2SV-M12
Connecting cable
With control electronics for 2 valves LF-, MF- and HF/LP 0.5 m 40 g 553121 MHJ9-KMH-0,5-MF
2.5 m 98 g 565519 MHJ9-KMH-2,5-MF
With control electronics for 2 valves HF 0.5 m 40 g 562170 MHJ9-KMH-0,5-HF